Chlorine Valve Accessories
The accessories ofChlorine Cylinder Valve KLINGER Brazil, are essential for the safe handling and transfer of chlorine between containers and piping systems.
Firstly, Chlorine Cylinder Valve and TubeFlexible Copper must be fitted to the Yoke Clamp. Right away, the Sealing Washer is placed at the outlet of the Valve, in order to prevent chlorine leakage in the connection with the Copper Flexible.
With the aid of the Valve Stem Operation Key, the Yoke Clamp must be tightened to secure the connection between the Chlorine Cylinder Valve and the Copper Flexible Tube. Furthermore, the valve can be opened and closed with the same key.
Yoke clamp
The yoke clamp (or Sergeant) is applied to make the connection between the valve of the 50kg chlorine cylinder / 68kg and 900kg at the copper flexible terminal.
Application
50kg chlorine cylinders / 68kg e 900kg, and flexible copper.
Building standards
NBR 17016;
Pamphlet 17 Chlorine Institute.

Valve stem operating switch
Wrench for opening and closing the chlorine cylinder valve and applying the yoke clamp to connect the valve to the copper hose.
Application
50KG chlorine cylinders / 68KG e 900KG, and yoke clamp.
Building standards
Recommended measures in the Pamphlet 1 Chlorine Institute.

Valve seal washer
The sealing washer is applied to the chlorine valve outlet, in order to prevent fluid leakage at the time of connection with the copper flexible (through the yoke or sergeant clamp).
It is essential to emphasize that each new connection requires the use of a new sealing gasket..
Application
50KG chlorine cylinders / 68KG e 900KG;
Pressure: 300 Psi;
Fluent: Chlorine – Cl 2 (gas or liquid).
Building standards
NBR 13295;
Pamphlet 95 Chlorine Institute.

Downloads
Data sheet – Chlorine Valve Accessories
Data sheet – Chlorine Valve Accessories (ES)
Also discover

Ammonia cylinder valve
Equipment designed to establish, check, and interrupt the flow of gas in its use or packaging operation, with opening and closing.